E-katalog skupiny BLOCK®
Circulating unit (CU) to be installed below suspended ceiling or onto movable box 110.04/C
Circulating units are used to supply filtered air to a workplace and to protect the product from ambient contamination.
The design of the circulating unit, together with suitable regulation, provides uniform airflow at the outlet under the unit, with the required speed in the range of 0.3 ÷ 0.45 m.s-1 (when air density ς = 1.2 kg.m3).
The protective effect is enhanced by attaching flexible or fixed screens along the perimeter of the unit.
When installing the circulating unit in areas without a defined class of cleanliness or in an environment with increased dust generation, a pre-filter is mounted at the suction inlet of the unit.
TECHNICAL DATA
Type |
---|
circulating unit (CU) to be installed below suspended ceiling or onto movable box |
A, B etc. - number of product change Change C - as of 03/2016 (fluid seal filters, touchscreen) |
CU size HEPA filter filtration class |
---|
CU dimensions 1250×625 mm |
CU dimensions 1250×1250 mm |
Atypical |
Suction design |
---|
upper suction |
Bottom suction from the room (with side structure) |
Suction via HVAC upper structure with side rectangular neck |
Suction via HVAC upper structure with upper round neck |
Suction via HVAC upper structure with upper square neck |
H13 class filtration |
H14 class filtration |
U15 class filtration |
Outlet design |
---|
laminarizator |
perforated metal sheet |
Lighting |
---|
without lighting |
with LED lighting tubes |
Lighting - only for the laminarizator version |
Material and surface finish |
---|
stainless steel AISI 304 SB |
steel sheet class 11, hue RAL 9016 |
Atypical execution |
---|
Typical execution |
Atypical execution |
Typical execution 0 - clear choice from the options Atypical execution Q - Atypical design, which can not be clearly identified by means of code |